ANALOG CARD 8-CHANNEL
ANALOG CARD 8-CHANNEL

ANALOG CARD 8-CHANNEL

ITEM CONTENTS
TECHNICAL  SPECIFICATIONS
RATED SUPPLY VOLTAGE 24vdc
SUPPLY VOLTAGE LIMITS 9...30 V
ANALOGUE INPUT TYPE CURRENT 4-20 ISOLATED
ANALOGUE INPUT NUMBER 8
ANALOGUE INPUT RESOLUTION 12 BITS
LOAD 100 OHM ON EACH INPUT
LSB VALUE 3.91 μA4...20 mA CURRENT
SAMPLING DURATION 1 MS
ABSOLUTE ACCURACY ERROR +/-0.5% OF FULL SCALE
TEMPERATURE DRIFT +/-0.01% FS/°C
REPEAT ACCURACY +/-0.5% FS
CURRENT CONSUMPTION 40 mA AT 24 VDC VIA EXTERNAL SUPPLY FULL LOAD
INSULATION BETWEEN INPUT AND SUPPLY AT 1.5KV
SURGE WITHSTAND CONFORMING TO IEC 61000-4-5
MOUNTING SUPPORT RAIL CONFORMING TO IEC 60715
SIZE IN MM 80h X 90w x 26d
NET WEIGHT 110 GM.
STANDARDS IEC 61010-2-201
RESISTANCE TO ELECTROSTATIC DISCHARGE CONFORMING TO IEC 61000-4-2
RESISTANCE TO ELECTROMAGNETIC FIELDS CONFORMING TO IEC 61000-4-3
RESISTANCE TO MAGNETIC FIELDS CONFORMING TO IEC 61000-4-8
RESISTANCE TO CONDUCTED DISTURBANCES IEC 61000-4-6
AMBIENT AIR TEMPERATURE FOR OPERATION 0...55°C
IP DEGREE OF PROTECTION IP20
COMMUNICATION ISOLATED RS485 MODBUS
BAUD RATE 2400,4800,9600,11200,22400
COMMUNICATION RATE 10 TIMES/SEC.
FLOW RATE M3/HR, M3/M, M3/S
TOTALIZER M3 (KL)

OVERVIEW

AE-Al-01 IS 8 CHANNELS ISOLATED 4-20ma INPUT MODULE, SIGNAL CONVERTER, DIN RAIL MOUNTING, USED FOR DATA ACQUISITION FOR VARIOUS SENSORS, STANDARD MODBUS PROTOCOL CONFIGURABLE WITH SOFTWARE,PLC,HMI,SCADA,OP SERVER ETC.

  1. CAN SELECT COM PART, BAUD RATE AND SLAVE ID.

  2. CALIBER PROCESS VALUE MINIMUM AND MAXIMUM AGAINST 4-20ma.

  3. CAN DO MA CALIBRATION.

  4. CAN READ TOTALIZER VALUE, EDIT, ACTIVE/DEACTIVATE AND OPTION FOR SAVE OR NOT.

  5. CAN SELECT m3/HOUR, m3/MINUTE, m3/SECOND.

MODBUS ADDRESS

SLAVE ID: 1(DEFAULT)

FUNCTION: READ INPUT REGISTERS (0x03)

BAUD RATE: 9600 (DEFAULT)

DATA BITS: 8 (DEFAULT)

PARITY: NONE (DEFAULT)

STOP BIT: 1(DEFAULT)

ma VALUE(4-20)

SL NO. FIELD REGISTER ADDRESS DATATYPE SCALE FACTOR TYPE
1 AI 0 0 LONG *100 READ
2 AI 1 2 LONG *100 READ
3 AI 2 4 LONG *100 READ
4 AI 3 6 LONG *100 READ
5 AI 4 8 LONG *100 READ
6 AI 5 10 LONG *100 READ
7 AI 6 12 LONG *100 READ
8 AI 7 14 LONG *100 READ
ACTUAL VALUE BASED ON START & SPAN
SL NO. FIELD REGISTER ADDRESS DATATYPE SCALE FACTOR TYPE
1 AI 0 16 LONG *100 READ
2 AI 1 18 LONG *100 READ
3 AI 2 20 LONG *100 READ
4 AI 3 22 LONG *100 READ
5 AI 4 24 LONG *100 READ
6 AI 5 26 LONG *100 READ
7 AI 6 28 LONG *100 READ
8 AI 7 30 LONG *100 READ
TOTALIZER VALUES
SL NO. FIELD REGISTER ADDRESS DATATYPE SCALE FACTOR TYPE
1 AI 0 32 LONG *1 READ
2 AI 1 34 LONG *1 READ
3 AI 2 36 LONG *1 READ
4 AI 3 38 LONG *1 READ
5 AI 4 40 LONG *1 READ
6 AI 5 42 LONG *1 READ
7 AI 6 44 LONG *1 READ
8 AI 7 46 LONG *1 READ